MAG6182II IP Network PA Center
Support 32 fire alarm signal access, support short circuit and 12V-24V signal.
32-way independent control, support adjacent zone alarm....

Send Inquiry Chat Now

User's Manual
Safety Precautions

11.jpgTo reduce the risk of electric shock or equipment damage, please follow the requirements below:
● Be sure to use a separate, three-wire power outlet with ground wire.
● If there is crushing, knotting or damaging to the power cord such as damage to the power cord, contact the dealer immediately. After replacing the power cord, the system should be powered off, which can cause electric shock and even fire.
● When servicing or cleaning the surface of the host, the power plug must be unplugged.
● When pulling the power plug, do not pull the power cord directly to prevent
the break, and prevent electric shock; don't place the flammable and explosive items near the host to prevent explosion and fire.
● The host should be placed horizontally; don't make it not tilt, invert, vertical- placed.
● The host should be placed in a dry and ventilated environment,. It needs to retain more than 5cm space in order to facilitate heat dissipation. Do not cover the host and do not press things heavy on the host.
● It is strictly forbidden to open the host.
● If you don't use it for a long time or it's rainstorm, please turn off the host power and unplug the host power plug.

Please note the following symbols:
22.jpgThe lightning triangular symbol indicates the risk of electric shock.
33.jpgThe exclamation point triangle symbol indicates important operational or maintenance instructions.

Preface
Thank you for choosing our products. All products have been rigorously tested before leaving the factory, which abide by the quality of commitment. This product is widely used in schools, gymnasiums, square venues, parks, parking lots, railway stations, airports, villas, shopping malls and other places It is the ideal choice for public broadcasting. In order to facilitate your installation, please read this manual before installation.

Product Description
The network fire collector is for collection of occasion’s monitoring, smoke detection and emergency handling areas. When an alarm signal is received, the network fire collector sends the signal to the server for forced insertion of the emergency broadcast state. It’s performance is sustainable, stable, efficient and reliable.

Features
● Support 32 fire alarm signal access, support short circuit and 12V-24V signal.
● 32-way independent control, support adjacent zone alarm.
● The forced activation area may be limited to the accident zone and may be extended to several adjacent zones, which are pre-programmed by the networked host.
● You can customize the alarm to play the sound through the management software.
● The same system can have multiple devices connected to the network; control area can be extended.
● 10 / 100M adaptive, support DHCP / static IP, support LAN and WAN.
● 32-way signal indicator on the panel shows the working status.
● 1U size, space-saving and lighter-weight; anodized aluminum alloy panel, good- looking and durable

Product Panel Description

44(001).jpg

55(001).jpg

66(001).jpg


Connection and installation
System Diagram

77 - 副本.jpg


Connection Demonstration

88(001).jpg


Instructions
signal input: The network fire detector rear panel can access 32 partitions; the input signal can be 5V-24V positive polarity signal or short circuit signal (input current less than 3mA). The positive signal is valid when the input logic setting switch is set to HIGH; the short circuit signal is valid when the set switch is set to LOW.
Total output: As long as there is an alarm signal input (any one or more), the device on the rear panel of the three-core jack OR GATE will be activated and output short-circuit signal.
Extended: The same system supports the device to have multiple connections to the network to achieve control of regional expansion.

Instillation
Push the product parallel to the cabinet, so that the mounting holes on both sides of the product are aligned with the mounting holes on both sides of the cabinet and fixed with screws. (As shown below)

99.jpg

Specification

Item

Specification

Channels

32

Way of display

LED

Support agreement

TCP/IP、UDP、ICMP、IGMP(Multicast)

Activate neighbor

Multiple, programmable

Trigger signal level

5V-24V

Protection

AC fuse×1

Input mode

Short circuit、12V~24V

Power input

~220V/50Hz

Network

RJ45(10/100M)

Size(high×Width×Depth)

44×430×213mm

Product Weight

2.3kg